American Alarms Blog

Des Moines adopting new fire codes soon

by Adam Jacobs 9/15/2020
I went to the Des Moines Fire Dept this morning to see what will be coming down the road for new codes.  Here's summary of what they expect.
 
IFC and IBC 2018 - Central Iowa Code Consortium expects to receive all comments and requests for amendments by mid-August.  New codes, with local amendments will be sent to local governments for approval by December.  Early adopters (including Des Moines) will approve by March 2019
All CICC jurisdictions must approve by December 2019.
Pella is newest member of the CICC, which is now 18 communities.
 
Other sections with notable updates:
 
sec 510 - Emergency Responder Radio Coverage - Des Moines is still accepting fire fighter phones where their radios don't work, but may soon require RF boosters (DAS systems) in areas where they can't get 95% reliable coverage.
 
Sec 901 - Integrated systems must be tested TOGETHER at least once every 10 years.  Fire alarm plus suppression, wet sprinkler, HVAC, etc.
 
Spaces under grandstands/bleachers that are at least 1000 square feet and enclosed, must have full sprinkler coverage.
 
Sec 903.3.1.2.3 - Attics intended for living space or storage - sprinkler required. also where eave of roof is 55ft or more above egress level and made of combustible materials
 
Residential cooking appliances (see UL 300)
 
Sec 907.2.1 - Group A fire alarm requirements - 300 total occupancy OR if any level ABOVE the egress level has occupancy of 100 or more.
 
Sec 1010 - Locking arrangements in Group E and Group B occupancy, delayed egress
 
Chapter 11 - Existing buildings
Sec 1103 - Bars (drinking establishments) that hold more than 300 people
Sec 1103.9 - CO detection requirements
 
Call American Alarms if you have any questions about what is required in your building.

| To the top |

Do wireless fire alarm systems really work?

by Adam Jacobs 9/15/2020

Wireless alarm systems have been around for over 30 years.  CWSI is the leader in commercial wireless fire alarm systems, for a number of reasons - wider acceptance, reliability, and experience.  They have been developing their low-frequency wide spectrum RF technology for over 30 years.  In some projects, wireless makes the most sense because it saves labor and can go where wires can't.  Attached is an article from fire protection engineer Lynn Nielson, PE.  This article demystifies many of the confusing aspects of wireless fire alarms.

cp-engineer-article.pdf (617.17 kb)

| To the top |

2018 I-codes focus on CO, integrated testing, and mass notification

by Adam Jacobs 9/15/2020

Today Honeywell's industry affairs expert Richard Roberts presented a summary of the relevant changes in the new 2018 i-codes (IBC, IFC, IMC, IPMC, IEBC, and IRC).  Some of the focus areas are carbon monoxide detection, integrated systems testing, and mass notification systems.  Some quick notes of importance for fire alarm design:

Section 901

Integrated testing of fire protection systems tied to other life safety systems.  Fire alarm and HVAC, sprinkler and fire alarm, suppression systems and fire alarm, fire doors/smoke dampers and fire alarm, and other integrated systems gain clearer direction for testing.

Section 907

- Group A occupancy (assembly) requires a manual system when 100 or more people occupy levels above the discharge level.

- Multiple-channel voice evacuation is required for high-rises over 120' above fire department access level.

- Strobes are required in all habitable spaces (like LR with pull-out couch) in hotels and apartments designated hearing-impaired/ADA.

- Manufacturer's maintenance recommendations will be enforced on smoke alarms, with a max life of 10 years.

Section 915

Some of the ambiguous language on placement of CO detectors has been replaced with clearer language.  CO detector required on ceiling above fuel-burning appliances.  More thought and direction is given to existing buildings and CO detection. 

NFPA 101 and NFPA 1 also added some new language and sections regarding CO detection for almost every type of public occupancy class.

New language like "...spaces served by the first supply air register from a fuel-burning HVAC system..." has been added to clarify placement of CO detectors.

Section 917 

Requirements for mass notifications systems, particularly those defined by an NFPA 72 Risk Analysis.

 

FOR  THE FULL PRESENTATION, SEE THE ATTACHED LINK BELOW.